House call today, a furnace wasn't heating, seems this usually happens on a bitter cold weekend, that's a holiday, and usually after any store that might have be open earlier is closed. Today's wasn't quite that bad, but I have to say it. Anyway, here's the run down from the phone conversation:
- Pilot was lit
- Thermostat was calling for heat
- Breakers were on
- Main burner wasn't coming on
I was thinking a bad limit, transformer, or gas valve (not much else on a simple pilot furnace)., But when I arrived I found the furnace was actually a HV (Spark) ignited furnace.
Sorry about the quality, cell phone in basement, at least I took a picture of it.
The Robertshaw sp715a control box:
- Turns on the pilot gas
- Jumps a spark until it senses a flame
- Turns on the main burner
Since it wasn't trying to light the pilot (audible clicking and a visible spark in the pilot area) it had detected that the pilot was lit, but for some reason the main burner was off. A quick check with a multimeter verified 28vac at the pilot terminal, and about 2vac at the main burner terminal. I was trying to pull the thermostat wire off the control when the main burner suddenly lit! Surprised, I let go and pulled my hand out as the burner shut off. I tried it again, confirming when I pulled on the wire (and flexed the PCB it was connected to) the burner came on.
You can't really see them in the picture, but 2 of the solder joints on the big black relay that controls the main burner were cracked. I had to run to a store to buy a soldering iron (a $6 firestarter), but it was quicker than driving home to solder them. I resoldered and reassembled the furnace. They've got heat and didn't have to buy a $100 module (or wait in a cold house until I could get one either).
Steve
UPDATE: A Few Links